All prices are subject to change due to supply chain fluctuation. We endeavour to keep the website updated where possible.

CFP Economy 8 Zone Conventional Fire Alarm Panel

£136.00 excl VAT

LPCB certified to EN54-2/4, C-TEC’s CFP 8 zone economy fire alarm panel offers an array of user and installer-friendly features at a very competitive price.

Supplied in an attractive flush or surface mountable plastic enclosure, it includes eight detector zones, four conventional sounder circuits, class change and alert inputs, four open collector outputs (fire, fault, reset and remote) and combined keypad/keyswitch entry.

Unlike our Standard CFP fire panel, the CFP708E-2 is NOT compatible with CFP repeaters, relay expansion boards or EN54-13 interface cards. It also has limited engineering functions.

  • Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB)
  • Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry
  • Manufactured by C-TEC in the UK
  • Eight detector zone circuits
  • Four conventional sounder circuits
  • Integral 1.5A EN54-4/A2 compliant switch mode PSU
  • Wide range of test and fault-finding facilities
  • Four open-collector outputs (Fire, Fault, Remote and Reset)
  • ‘Class change’ and alert inputs
  • Installer-friendly design
  • Attractive flush or surface mountable plastic lid and enclosure – no bezel required
  • Low 25mA quiescent current
  • Multiple indicators
  • No system expansion connections
  • Fully compatible with C-TEC’s ActiV range of conventional fire detectors
Approvals/certificationsCertified to EN54-2/4 by the LPCB (176b) / (0832-CPR-F0576).
Mains supply230V 50/60Hz.
Mains rated current350mA maximum.
Internal power supply19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current25mA (mains failed, internal sounder active, PSU & gen fault LED lit).
Max battery size and type2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits8 (Max. length per circuit is 500m).
Call point resistor value470 to 680Ω.
Max. devices per detector zone25 detectors (or 32 detectors/manual call points combined).
No. of conventional sounder circuits4 (Max. length per circuit is 500m).
EOL resistor value6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage27V max, 20V min (final battery voltage).
Max. sounder output current4 x 200mA (800mA total).
Auxiliary relaysNone.
Open collector outputsFour: (1) Aux. Fire; (2) Fault; (3) Reset (Active during reset cycle); (4) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc).
Other outputs24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
Auxiliary inputsTwo: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
Engineer (AL3) functionsInvoke One Man Walk Test; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities.
Expansion connectionsNone. The CFP Economy panel CAN NOT be extended with CFP repeaters, relay cards or EN54-13 interface boards.
Product dimensions (mm)380 W x 235 H x D 96mm.
Construction & finishPlastic lid and base; RAL7035 textured.
IP RatingIP30.
Weight1.75kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.